This product is capable of real-time monitoring of environmental temperature, humidity, and barometric pressure. It transmits data to the main control device via the RS485 communication protocol. It is widely used in industrial processes, meteorological monitoring, hydrology, water conservancy, geological exploration, and other fields.
1.Product Introduction
Figure 1
This product is capable of real-time monitoring of environmental temperature, humidity, and barometric pressure. It transmits data to the main control device via the RS485 communication protocol. It is widely used in industrial processes, meteorological monitoring, hydrology, water conservancy, geological exploration, and other fields.
Key Features:
- High quality and stability
- Integrated measurement of temperature, humidity, and barometric pressure
- RS485 interface and Modbus-RTU standard communication protocol
- Reverse polarity protection and overvoltage protection
- Fully sealed stainless steel structure with IP68 protection
2. Technical Specifications
2.1 Main Performance Indicators
Performance Indicators | Temperature | Humidity | Barometric Pressure |
Accuracy | ±0.1℃ (see Table 1) | 1.5 %RH ,(see Table 2) | ±50Pa |
Range | -40~85℃ | 0~100%RH | 300~1250hPa |
Resolution | 0.1℃ | 1%RH | 1Pa |
Table 1
Table 2
Table 3
2.2 Other Parameters
Electrical Characteristics | |
Supply Voltage | DC5~30V |
Power Protection | Reverse polarity and over-voltage protection |
Output Method | RS485/Modbus-RTU protocol |
Structural Characteristics | |
Measurement Medium | Compatible with stainless steel and fluororubber |
Housing Material | Stainless steel 316L |
Cable Material | PVC or polyurethane |
Cable Specifications | Φ7.6mm ,Φ7.6mm, custom length |
Environmental Characteristics | |
Protection Level | IP68 |
Operating Environment | Operating temperature: -40 to 85℃, relative humidity: 0 to 100%RH |
Figure
2.3 Power Supply and RS485 Wiring Definitions**
No. | Wire Color | Definition |
1 | Red | 5-30V+ |
2 | Blue | RS485+ |
3 | Green | RS485- |
4 | Yellow | GND |
Figure 3
2.4 Dimensions (Unit: mm)
Figure 4
Figure 5
3. User Instructions
3.1 Connecting to a Computer
Refer to Table 3 for wiring. The following accessories are required to connect to a computer:
- RS232 to RS485 converter
- USB to RS232 converter
- USB to RS485 converter
Connection Method:
- Connect the blue wire (RS485-A) to the converter's RS485+ (T+).
- Connect the green wire (RS485-B) to the converter's RS485- (T-).
- Plug the USB cable directly into the computer's USB port. The corresponding COM port can be viewed in the device manager and used in the computer software.
3.2 Communication Protocol**
The supported communication protocol is MODBUS-RTU. After external power is connected, the device can be operated via computer software or a Modbus host (e.g., RTU device). The device uses an industrial-grade RS485 communication interface, operating in half-duplex master-slave mode with a transmission distance of up to 1200 meters. The default baud rate is 9600, with no parity, 1 stop bit, and 8 data bits. After connecting to a computer or RTU device, communication can be performed using function codes 03H and 10H in the Modbus-RTU protocol.
Get Device Address | |
Modbus Command | FF 6E 00 12 00 01 9C 18 |
Return Value | FF 6E 02 00 01 4C FC |
Data Parsing | Device address is 0X00 0X01 |
Table 4
Get Temperature, Humidity, and Barometric Pressure Data | |
Modbus Command | 01 03 00 03 00 05 75 C9 |
Return Value | 01 03 0A 00 D9 00 D8 00 17 00 01 76 73 C9 68 |
Data Parsing | See Table 7 |
Table 5
Modify Device Address | |
Modbus Command | 01 10 00 12 00 01 02 00 02 24 E3 |
Return Value | 01 10 00 12 00 01 A1 CC |
Data Parsing | Address modified to 0X0002 |
Table 6
Register Address | Name | Definition |
0x00~ 0x02 | Reserved | Not readable or writable |
0x03 | Temperature 1 | Barometric pressure sensor temperature data *10 (16-bit signed integer) |
0x04 | Temperature 2 | Temperature and humidity sensor temperature data *10 (16-bit signed integer) |
0x05 | Humidity | Humidity data (16-bit unsigned integer) |
0x06~ 0x07 | Barometric pressure | Barometric pressure data (32-bit unsigned integer) |
0x0C~ 0x0E | Serial No. | Device serial number |
0x0F~ 0x10 | Manufacturing Date | Device manufacturing date |
0x11 | Version Number | Device version number |
0x12 | Address | Device communication address (0-255, default is 1) |
0x13 | Baud Rate | Serial port baud rate (default is 9600) |
Table 7
Contact:Roxy Deng
Phone:+8617794001501
Tel:+8617794001501
Email:roxy@besteetech.com
Add:Weibin District, Baoji, Shaanxi Province, China